What device may be used to ensure that air is flowing through a duct before an electric strip is energized

Respuesta :

Perplexed20
Perplexed20 Perplexed20
  • 01-03-2021

Answer:

Most commonly used air flow proving interlocks are:

  • differential pressure air flow switch.  Contact changes state based on duct static vs. atmosphere outside the duct or dp across a fan inlet to outlet
  • CT relay.  Current transformer relay that changes state from 0 to 1 open/closed when amp draw on a blower motor exceeds the trip setpoint.